PVC/CPVC

Urecon Pre-Insulated PVC Water Pipe Class 100 DR 25
Dimensions 100 mm (4 in) to 300 mm (12 in)
AWWA-C900 Ductile Iron dimensional PVC pipe

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Class 100, 600 kPa (100 psi), DR 25
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
100 4 122 4.80 196 7.75 229 9.00 112 4.42 4.88 0.192 4.97 3.34
150 6 175 6.90 247 9.75 279 11.00 161 6.34 7.09 0.279 8.59 5.78
200 8 230 9.05 304 12.00 337 13.25 212 8.33 9.20 0.362 13.28 8.93
250 10 281 11.10 355 14.00 394 15.50 260 10.21 11.28 0.444 18.90 12.71
300 12 335 13.20 406 16.00 445 17.50 308 12.14 13.42 0.528 25.75 17.32
  1. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  2. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  5. Insulated pipe available in standard industry lengths of 6.1 m (20 ft) with bell and spigot joints.
  6. Class designation indicates working pressure in PSIG at 23°C (73.4°F).
  7. Pipe conforms to AWWA C900-81 where applicable and is certified to CSA B137.3 and NQ 3624-250.

Urecon Pre-Insulated PVC Water Pipe Class 150 DR 18
Dimensions 100 mm (4 in) to 300 mm (12 in)
AWWA-C900 Ductile Iron dimensional PVC pipe

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Class 150, 1039 kPa (150 psi), DR 18
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
100 4 122 4.80 196 7.75 229 9.00 108 4.25 6.79 0.267 5.98 4.02
150 6 175 6.90 247 9.75 279 11.00 155 6.10 9.73 0.383 10.62 7.14
200 8 230 9.05 304 12.00 337 13.25 203 7.99 12.78 0.503 16.85 11.33
250 10 281 11.10 355 14.00 394 15.50 249 9.80 15.68 0.617 24.34 16.38
300 12 335 13.20 406 16.00 445 17.50 296 11.65 18.62 0.733 34.20 23.00
  1. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  2. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  5. Insulated pipe available in standard industry lengths of 6.1 m (20 ft) with bell and spigot joints.
  6. Class designation indicates working pressure in PSIG at 23°C (73.4°F).
  7. Pipe conforms to AWWA C900-81 where applicable and is certified to CSA B137.3 and NQ 3624-250.

Urecon Pre-Insulated PVC Large Diameter Water Pipe DR 41
Dimensions 350 mm (14 in) to 500 mm (20 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Large Diameter Pipe DR 41, 698 kPa (100 psi)
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 50 mm 2 in mm in mm in kg/m lbs/ft
350 14 389 15.30 495 19.50 370 14.55 9.47 0.373 22.85 15.28
400 16 442 17.40 546 21.50 420 16.55 10.77 0.424 28.67 19.18
450 18 495 19.50 603 23.75 471 18.55 12.06 0.475 35.11 23.48
500 20 547 21.60 654 25.75 522 20.55 13.38 0.527 41.99 28.08
  1. Insulation thickness 50 mm (2 in) minimum; other thicknesses available on request. CAUTION: Insulation outside diameter may be larger than indicated above; if critical, verify with Urecon.
  2. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulated pipe available in standard industry lengths of 6.1 m (20 ft) with bell and spigot joints.
  5. Data and size availability may vary from one manufacturer to another.
  6. Reference specifications (core pipe): AWWA C905 where applicable, CSA B137.3 and NQ 3624-250.

Urecon Pre-Insulated PVC Large Diameter Water Pipe DR 25
Dimensions 350 mm (14 in) to 500 mm (20 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Large Diameter Pipe DR 25, 1137 kPa (165 psi)
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 50 mm 2 in mm in mm in kg/m lbs/ft
350 14 389 15.30 495 19.50 358 14.08 15.54 0.610 33.72 22.59
400 16 442 17.40 546 21.50 407 16.00 17.68 0.700 42.76 28.65
450 18 495 19.50 603 23.75 456 17.94 19.81 0.780 52.93 35.46
500 20 547 21.60 654 25.75 505 19.87 21.94 0.864 64.23 43.03
  1. Insulation thickness 50 mm (2 in) minimum; other thicknesses available on request. CAUTION: Insulation outside diameter may be larger than indicated above; if critical, verify with Urecon.
  2. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulated pipe available in standard industry lengths of 6.1 m (20 ft) with bell and spigot joints.
  5. Data and size availability may vary from one manufacturer to another.
  6. Reference specifications (core pipe): AWWA C905 where applicable, CSA B137.3 and NQ 3624-250.

Urecon Pre-Insulated PVC Large Diameter Water Pipe DR 18
Dimensions 350 mm (14 in) to 500 mm (20 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Large Diameter Pipe DR 18, 1620 kPa (235 psi)
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 50 mm 2 in mm in mm in kg/m lbs/ft
350 14 389 15.30 495 19.50 345 13.60 21.59 0.850 45,43 30.49
400 16 442 17.40 546 21.50 393 15.47 24.56 0.967 57,63 38.68
450 18 495 19.50 603 23.75 440 17.33 27.51 1.083 71,32 47.87
500 20 547 21.60 654 25.75 488 19.20 30.48 1.200 86.18 57.78

  1. Insulation thickness 50 mm (2 in) minimum; other thicknesses available on request CAUTION: Insulation outside diameter may be larger than indicated above; if critical, verify with Urecon.
  2. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulated pipe available in standard industry lengths of 6.1 m (20 ft) with bell and spigot joints.
  5. Data and size availability may vary from one manufacturer to another.
  6. Pipe conforms to AWWA C905 where applicable and is certified to CSA B137-3 and NQ 3624-250.

Urecon Pre-Insulated PVC Water Pipe Series 100 SDR 41
Dimensions 40 mm (1.5 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Series 100, 690 kPa (100 psi), DR 41
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
40 1.5 48 1.90 127 5.00 155 6.13 See Series 160
50 2 60 2.38 139 5.50 165 6.50 See Series 160
75 3 89 3.50 171 6.75 196 7.75 See Series 125
100 4 114 4.50 196 7.75 228 9.00 108 4.28 2.79 0.110 3.76 2.53
150 6 168 6.63 247 9.75 279 11.00 160 6.30 4.12 0.162 6.08 4.09
200 8 219 8.63 304 12.00 337 13.25 208 8.21 5.33 0.210 8.95 6.02
250 10 273 10.75 355 14.00 394 15.50 259 10.23 6.66 0.262 12.64 8.50
300 12 324 12.75 406 16.00 445 17.50 307 12.13 7.90 0.311 16.77 11.28
  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  7. Solvent weld couplings and bell and spigot joints are both available in most cases.
  8. Series designation indicates working pressure in PSIG at 23°C (73.4°F).
  9. Data and sizes available and jointing method may vary from one pipe manufacturer to another,
  10. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and AWWA C905 in 350 to 500 mm (14 to 20 in) sizes.

Urecon Pre-Insulated PVC Water Pipe Series 125 SDR 32.5
Dimensions 40 mm (1.5 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Series 125, 860 kPa (125 psi), DR 32.5
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
40 1.5 48 1.90 127 5.00 155 6.13 See Series 160
50 2 60 2.38 139 5.50 165 6.50 See Series 160
75 3 89 3.50 171 6.75 196 7.75 83 3.28 2.74 0.108 2.97 2.00
100 4 114 4.50 196 7.75 228 9.00 108 4.28 3.51 0.138 4.10 2.76
150 6 168 6.63 247 9.75 279 11.00 160 6.30 5.18 0.204 6.87 4.62
200 8 219 8.63 304 12.00 337 13.25 205 8.09 6.76 0.266 10.32 6.94
250 10 273 10.75 355 14.00 394 15.50 256 10.09 8.41 0.331 14.83 9.97
300 12 324 12.75 406 16.00 445 17.50 301 11.87 9.96 0.392 19.82 13.33

  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  7. Solvent weld couplings and bell and spigot joints are both available in most cases.
  8. Series designation indicates working pressure in PSIG at 23°C (73.4°F).
  9. Data and sizes available and jointing method may vary from one pipe manufacturer to another,
  10. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and AWWA C905 in 350 to 500 mm (14 to 20 in) sizes.

Urecon Pre-Insulated PVC Water Pipe Series 160 SDR 26
Dimensions 40 mm (1.5 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Series 160, 1103 kPa (160 psi), DR 26
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
40 1.5 48 1.90 127 5.00 155 6.13 44 1.74 2.03 0.080 1.98 1.33
50 2 60 2.38 139 5.50 165 6.50 56 2.19 2.31 0.091 2.17 1.46
75 3 89 3.50 171 6.75 196 7.75 82 3.22 3.43 0.135 3.23 2.17
100 4 114 4.50 196 7.75 228 9.00 105 4.13 4.39 0.173 4.54 3.05
150 6 168 6.63 247 9.75 279 11.00 155 6.09 6.48 0.255 7.85 5.28
200 8 219 8.63 304 12.00 337 13.25 201 7.92 8.43 0.332 11.99 8.06
250 10 273 10.75 355 14.00 394 15.50 251 9.87 10.49 0.413 17.38 11.69
300 12 324 12.75 406 16.00 445 17.50 298 11.72 12.40 0.488 23.45 15.77
  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  7. Solvent weld couplings and bell and spigot joints are both available in most cases.
  8. Series designation indicates working pressure in PSIG at 23°C (73.4°F).
  9. Data and sizes available and jointing method may vary from one pipe manufacturer to another,
  10. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and AWWA C905 in 350 to 500 mm (14 to 20 in) sizes.

Urecon Pre-Insulated PVC Water Pipe Series 200 SDR 21
Dimensions 40 mm (1.5 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Series 200, 1380 kPa (200 psi), DR 21
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kg/m lbs/ft
40 1.5 48 1.90 127 5.00 155 6.13 44 1.72 2.29 0.090 2.02 1.36
50 2 60 2.38 139 5.50 165 6.50 56 2.15 2.87 0.113 2.30 1.55
75 3 89 3.50 171 6.75 196 7.75 79 3.12 4.24 0.167 3.52 2.37
100 4 114 4.50 196 7.75 228 9.00 103 4.07 5.44 0.214 5.04 3.39
150 6 168 6.63 247 9.75 279 11.00 152 5.99 8.00 0.315 8.97 6.03
200 8 219 8.63 304 12.00 337 13.25 198 7.80 10.44 0.411 13.89 9.34
250 10 273 10.75 355 14.00 394 15.50 247 9.73 13.00 0.512 20.37 13.70
300 12 324 12.75 406 16.00 445 17.50 293 11.54 15.42 0.607 28.83 19.39

  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  7. Solvent weld couplings and bell and spigot joints are both available in most cases.
  8. Series designation indicates working pressure in PSIG at 23°C (73.4°F).
  9. Data and sizes are available and jointing method may vary from one pipe manufacturer to another,
  10. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and AWWA C905 in 350 to 500 mm (14 to 20 in) sizes.

Urecon Pre-Insulated PVC Schedule 40 PVC Pressure Pipe
Dimensions 25 mm (1 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Schedule 40 PVC
Insulation
Thickness
Avg.
Pipe I.D.
Min. Wall
Thickness

Pressure
Rating

Total
Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kPa PSI kg/m lbs/ft
25 1 33 1.32 108 4.25 133 5.25 26 1.029 3.38 0.133 3100 450 1.13 0.76
40 1.5 48 1.90 127 5.00 155 6.13 40 1.590 3.68 0.145 2280 330 1.46 0.98
50 2 60 2.38 139 5.50 165 6.50 52 2.047 3.90 0.154 1930 280 1.74 1.17
65 2.5 73 2.88 155 6.13 181 7.13 62 2.445 5.16 0.203 2070 300 2.49 1.67
75 3 88 3.50 171 6.75 196 7.75 77 3.042 5.48 0.216 1790 260 3.13 2.10
100 4 114 4.50 196 7.75 228 9.00 101 3.998 6.02 0.237 1520 220 4.32 2.90
150 6 168 6.63 247 9.75 279 11.00 153 6.031 7.10 0.280 1310 180 6.99 4.70
200 8 219 8.63 304 12.00 337 13.25 201 7.941 8.18 0.322 1240 160 10.24 6.88
250 10 273 10.75 355 14.00 394 15.50 253 9.976 9.26 0.365 1103 140 14.11 9.48
300 12 323 12.75 406 16.00 445 17.50 302 11.888 10.30 0.406 965 130 18.25 12.26
  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 3.05 m (10 ft) or 6.1 m (20 ft).
  7. Jointing is by means of solvent weld couplings.
  8. Pressure rating is at 23°C (73.4°F) and varies according to the diameter of the pipe.
  9. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and NSF # 14, # 61.

Urecon Pre-Insulated PVC Schedule 80 PVC Pressure Pipe
Dimensions 25 mm (1 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Schedule 80 PVC
Insulation
Thickness
Avg.
Pipe I.D.
Min. Wall
Thickness

Pressure
Rating

Total
Weight
mm in mm in 40 mm 1.5 in 50 mm 2 in mm in mm in kPa PSI kg/m lbs/ft
25 1 33 1.32 108 4.25 133 5.25 23.8 0.940 4.8 0.190 4343 630 1.25 0.84
40 1.5 48 1.90 127 5.00 155 6.13 37.5 1.476 5.4 0.212 3240 470 1.71 1.15
50 2 60 2.38 139 5.50 165 6.50 48.7 1.918 5.9 0.231 2758 400 2.13 1.43
65 2.5 73 2.88 155 6.13 181 7.13 58.3 2.294 7.4 0.293 2930 425 3.01 2.02
75 3 88 3.50 171 6.75 196 7.75 72.7 2.864 8.1 0.318 2585 375 3.88 2.61
100 4 114 4.50 196 7.75 228 9.00 96.2 3.786 9.1 0.357 2206 320 5.51 3.70
150 6 168 6.63 247 9.75 279 11.00 145.1 5.714 11.6 0.458 1861 280 9.72 6.53
200 8 219 8.63 304 12.00 337 13.25 192.3 7.570 13.5 0.530 1723 250 14.44 9.70
250 10 273 10.75 355 14.00 394 15.50 241.1 9.492 16.0 0.629 1585 230 20.11 13.51
300 12 323 12.75 406 16.00 445 17.50 286.8 11.290 18.5 0.728 1585 230 28.19 18.94
  1. Other sizes available on request.
  2. Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
  5. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  6. Insulated pipe available in standard industry lengths of 3.05 m (10 ft) or 6.1 m (20 ft).
  7. Jointing is by means of solvent weld couplings.
  8. Pressure rating is at 23°C (73.4°F) and varies according to the diameter of the pipe.
  9. Reference specifications (core pipe): ASTM D-2241, CSA B137.3 and NSF # 14, # 61.

Urecon Pre-Insulated PVC Schedule 40 CPVC Pipe For Hot Water
Dimensions (IPS) 13 mm (.50 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Schedule 40 CPVC
Insulation
Thickness
Avg.
Pipe I.D.
Min. Wall
Thickness

Pressure
Rating

Total
Weight
mm in mm in 40 mm 1.5 in mm in mm in kPa PSI kg/m lbs/ft
13 0.5 21 0.84 108 4.25 15 0.608 3.05 0.12 4137 600 0.98 0.60
25 1 33 1.32 108 4.25 26 1.033 3.56 0.14 3102 450 1.13 0.76
40 1.5 48 1.90 127 5.00 40 1.592 3.81 0.15 2275 330 1.53 1.03
50 2 60 2.38 139 5.50 52 2.049 4.06 0.16 1930 280 1.85 1.24
65 2.5 73 2.88 155 6.13 62 2.445 5.59 0.22 2068 300 2.63 1.77
75 3 88 3.50 171 6.75 77 3.042 5.84 0.23 1792 260 3.32 2.23
100 4 114 4.50 196 7.75 101 3.998 6.35 0.25 1516 220 4.58 3.08
150 6 168 6.63 247 9.75 153 6.031 7.62 0.30 1241 180 7.47 5.02
200 8 219 8.63 304 12.00 201 7.943 8.64 0.34 1103 160 10.95 7.36
250 10 273 10.75 355 14.00 253 9.976 9.91 0.39 965 140 14.82 9.96
300 12 323 12.75 406 16.00 302 11.890 10.92 0.43 896 130 19.59 13.16

  1. Other sizes available on request.
  2. Insulation thickness for hot water 40 mm (1.5 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  5. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  6. Jointing is by means of solvent weld couplings.
  7. Pressure rating is at 23°C (73.4°F) and varies according to the diameter of the pipe. See derating factors for higher temperature operation.
  8. Reference specifications (core pipe): ASTM D1784 / F441 for solvent weld # 40 CPVC pipe.

Urecon Pre-Insulated PVC Schedule 80 CPVC Pipe For Hot Water
Dimensions (IPS) 13 mm (.50 in) to 300 mm (12 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. Schedule 80 CPVC
Insulation
Thickness
Avg.
Pipe I.D.
Min. Wall
Thickness

Pressure
Rating

Total
Weight
mm in mm in 40 mm 1.5 in mm in mm in kPa PSI kg/m lbs/ft
13 0.5 21 0.84 108 4.25 13.4 0.528 4.0 0.156 5860 850 0.97 0.65
25 1 33 1.32 108 4.25 23.8 0.940 4.8 0.190 4343 630 1.31 0.88
40 1.5 48 1.90 127 5.00 37.5 1.476 5.4 0.212 3240 470 1.82 1.22
50 2 60 2.38 139 5.50 48.7 1.918 5.9 0.231 2758 400 2.26 1.52
65 2.5 73 2.88 155 6.13 58.3 2.294 7.4 0.293 2930 425 3.21 2.16
75 3 88 3.50 171 6.75 72.7 2.864 8.1 0.318 2585 375 4.15 2.79
100 4 114 4.50 196 7.75 96.2 3.786 9.1 0.357 2206 320 5.88 3.95
150 6 168 6.63 247 9.75 145.1 5.714 11.6 0.458 1861 270 10.43 7.01
200 8 219 8.63 304 12.00 192.3 7.570 13.5 0.530 1723 250 15.52 10.43
250 10 273 10.75 355 14.00 241.1 9.492 16.0 0.629 1585 230 21.65 14.55
300 12 323 12.75 406 16.00 286.8 11.290 18.5 0.728 1585 230 30.43 20.42
  1. Other sizes available on request.
  2. Insulation thickness for hot water 40 mm (1.5 in) minimum; other thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  5. Insulated pipe available in standard industry lengths of 6.1 m (20 ft).
  6. Jointing is by means of solvent weld couplings.
  7. Pressure rating is at 23°C (73.4°F) and varies according to the diameter of the pipe. See derating factors for higher temperature operation.
  8. Reference specifications (core pipe): ASTM D1784 / F441 for solvent weld # 80 CPVC pipe.

Urecon Pre-Insulated PVC Sewer Pipe DR 35
Dimensions 100 mm (4 in) to 500 mm (20 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. DR 35
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 50 mm 2 in mm in mm in kg/m lbs/ft
100 4 107 4.22 229 9.00 100 3.97 3.06 0.125 3.84 2.58
135 5 143 5.64 248 9.75 135 5.31 4.10 0.161 4.83 3.49
150 6 160 6.28 279 11.00 150 5.92 4.57 0.180 6.28 4.22
200 8 213 8.40 337 13.25 201 7.92 6.10 0.240 9.55 6.42
250 10 267 10.50 394 15.50 251 9.90 7.62 0.300 13.98 9.40
300 12 318 12.50 445 17.50 299 11.78 9.07 0.360 18.50 12.44
375 15 389 15.30 495 19.50 367 14.43 11.09 0.437 26.25 17.62
450 18 475 18.701 603 23.75 446 17.63 13.61 0.536 37.73 25.32
525 21 560 22.047 679 26.75 528 20.78 16.00 0.632 50.65 33.99
  1. Insulation thickness 50 mm (2 in) minimum; other thicknesses available on request.
  2. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Standard industry lengths of 4 m (13 ft).
  5. Data and size availability may vary from one manufacturer to another.
  6. Reference specifications (core pipe): ASTM D-3034, CSA B182.2., NQ3624-130 and NQ3624-135.

Urecon Pre-Insulated PVC Sewer Pipe DR 28
Dimensions 100 mm (4 in) to 150 mm (6 in)

Nominal
Pipe Size
Outside
Pipe Dia.
Insulation O.D. DR 28
Insulation Thickness Avg. Pipe I.D. Min. Wall Thickness Total Weight
mm in mm in 50 mm 2 in mm in mm in kg/m lbs/ft
100 4 107 4.22 229 9.00 99 3.91 3.81 0.150 4.13 2.78
125 5 143 5.64 248 9.75 133 5.24 5.11 0.201 6.20 4.17
150 6 160 6.28 279 11.00 148 5.83 5.69 0.224 7.05 4.74
  1. Insulation thickness 50 mm (2 in) minimum; other thicknesses available on request.
  2. Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
  3. Insulation thickness for Latin America/Caribbean (UreconRED and Urecon BLUE) nominal 25 to 37mm (1 to 1.5 in.) depending on diameter; other thicknesses available upon request.
  4. Standard industry lengths of 4 m (13 ft).
  5. Data and size availability may vary from one manufacturer to another.
  6. Reference specifications (core pipe): ASTM D-3034, NQ3624-130 and CSA B182,2.