Ductile Iron
Urecon Pre-Insulated Ductile Iron Pipe Class 350
Dimensions 75 mm (3 in) to 500 mm (20 in)
Nominal Pipe Size |
Outside Pipe Dia. |
Insulation O.D. | Class 350, 2413 kPa (350 psi) | ||||||||||
Insulation Thickness | Avg. Pipe I.D. | Min. Wall Thickness | Total Weight | ||||||||||
mm | in | mm | in | 40 mm | 1.5 in | 50 mm | 2 in | mm | in | mm | in | kg/m | lbs/ft |
75 | 3 | 100 | 3.96 | 181 | 7.13 | 197 | 7.75 | 88 | 3.46 | 6.35 | 0.250 | 15.53 | 10.42 |
100 | 4 | 122 | 4.80 | 196 | 7.75 | 229 | 9.00 | 109 | 4.30 | 6.35 | 0.250 | 19.05 | 12.79 |
150 | 6 | 175 | 6.90 | 247 | 9.75 | 279 | 11.00 | 162 | 6.40 | 6.35 | 0.250 | 27.58 | 18.51 |
200 | 8 | 230 | 9.05 | 304 | 12.00 | 337 | 13.25 | 217 | 8.55 | 6.35 | 0.250 | 36.24 | 24.32 |
250 | 10 | 281 | 11.10 | 355 | 14.00 | 394 | 15.50 | 269 | 10.58 | 6.60 | 0.260 | 46.37 | 31.12 |
300 | 12 | 335 | 13.20 | 406 | 16.00 | 445 | 17.50 | 321 | 12.64 | 7.11 | 0.280 | 58.91 | 39.54 |
350 | 14 | 389 | 15.30 | N/A | N/A | 495 | 19.50 | 373 | 14.68 | 7.87 | 0.310 | 75.69 | 50.80 |
400 | 16 | 442 | 17.40 | N/A | N/A | 546 | 21.50 | 425 | 16.72 | 8.64 | 0.340 | 93.60 | 62.82 |
450 | 18 | 495 | 19.50 | N/A | N/A | 603 | 23.75 | 477 | 18.78 | 9.14 | 0.360 | 104.79 | 70.33 |
500 | 20 | 549 | 21.60 | N/A | N/A | 654 | 25.75 | 529 | 20.84 | 9.65 | 0.380 | 128.81 | 86.45 |
- Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
- Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
CAUTION: Insulation outside diameter may be larger than indicated above; if critical, verify with Urecon. - Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
- Insulated pipe available in standard industry lengths.
- Weights indicated are for push on joints with cement lining.
- Data may vary slightly from one manufacturer to another.
- Reference specifications (core pipe) ANSI A21-51, AWWA C-151, NQ 3623-085.
Urecon Pre-Insulated Ductile Iron Pipe Class 300
Dimensions 350 mm (14 in) to 500 mm (20 in)
Nominal Pipe Size |
Outside Pipe Dia. |
Insulation O.D. | Class 300, 2068 kPa (300 psi) | ||||||||||
Insulation Thickness | Avg. Pipe I.D. | Min. Wall Thickness | Total Weight | ||||||||||
mm | in | mm | in | 40 mm | 1.5 in | 50 mm | 2 in | mm | in | mm | in | kg/m | lbs/ft |
350 | 14 | 389 | 15.30 | N/A | N/A | 495 | 19.50 | 373 | 14.70 | 7.62 | 0.300 | 73.61 | 49.40 |
400 | 16 | 442 | 17.40 | N/A | N/A | 546 | 21.50 | 426 | 16.76 | 8.13 | 0.320 | 88.68 | 59.52 |
450 | 18 | 495 | 19.50 | N/A | N/A | 603 | 23.75 | 478 | 18.82 | 8.64 | 0.340 | 104.79 | 70.33 |
500 | 20 | 549 | 21.60 | N/A | N/A | 654 | 25.75 | 530 | 20.88 | 9.14 | 0.360 | 122.85 | 82.45 |
- Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
- Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
CAUTION: Insulation outside diameter may be larger than indicated above; if critical verify with Urecon. - Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
- Insulated pipe available in standard industry lengths.
- Weights indicated are for push on joints with cement lining.
- Data may vary slightly from one manufacturer to another.
- Reference specifications (core pipe) ANSI A21-51, AWWA C-151, NQ 3623-085.
Urecon Pre-Insulated Ductile Iron Pipe Class 250
Dimensions 350 mm (14 in) to 500 mm (20 in)
Nominal Pipe Size |
Outside Pipe Dia. |
Insulation O.D. | Class 250, 1723 kPa (250 psi) | ||||||||||
Insulation Thickness | Avg. Pipe I.D. | Min. Wall Thickness | Total Weight | ||||||||||
mm | in | mm | in | 40 mm | 1.5 in | 50 mm | 2 in | mm | in | mm | in | kg/m | lbs/ft |
350 | 14 | 389 | 15.30 | N/A | N/A | 495 | 19.50 | 374 | 14.74 | 7.11 | 0.280 | 69.29 | 46.50 |
400 | 16 | 442 | 17.40 | N/A | N/A | 546 | 21.50 | 427 | 16.80 |
7.62 | 0.300 | 83.92 | 56.32 |
450 | 18 | 495 | 19.50 | N/A | N/A | 603 | 23.75 | 480 |
18.88 | 7.87 | 0.310 | 96.75 | 64.93 |
500 | 20 | 549 | 21.60 | N/A | N/A | 654 | 25.75 | 532 | 20.94 | 8.38 | 0.330 | 113.91 | 76.45 |
- Insulation thickness for freeze protection 50 mm (2 in) minimum; other thicknesses available on request.
- Insulation thickness for chilled water 40 mm (1.5 in) minimum; other thicknesses available on request.
CAUTION: Insulation outside diameter may be larger than indicated above; if critical verify with Urecon. - Jacketing 1.27 mm (50 mils) thick polyethylene; other types and thicknesses available on request.
- Insulated pipe available in standard industry lengths.
- Weights indicated are for push on joints with cement lining.
- Data may vary slightly from one manufacturer to another.
- Reference specifications (core pipe) ANSI A21-51, AWWA C-151, NQ 3623-085.